Maintaining an aging combined cycle plant ain’t what it used to be
October 27, 2026
9 min read
Share To:

Plant maintenance has changed markedly over the last decade. Where baseload operation of combined cycle plants used to be the norm, cycling is now in vogue. In some cases, facilities designed to be running 8,000 hours per year have been changed to a peaking or dispatch arrangement.
Sand Lake Energy Center (SLEC) in Orlando, Florida, is a good example. Built in 1993, it ran almost continuously as a cogeneration facility, providing 114.5 megawatts (MW) of baseload output and up to 125 MW at peak times. That continued until its power purchase agreement (PPA) expired at the end of 2023. It has now switched to dispatch power, operating a few days each month under its new owners, Florida Municipal Power Agency (FMPA), a wholesale power agency owned by 33 municipal electric utilities throughout Florida.
What does this mean on the maintenance side? Danny Slade, maintenance manager at SLEC, said he’s gone from constantly monitoring equipment to spending more time with FMPA executives to decide where the plant needs investment to better handle cycling and extend the life of an aging asset.
Immediate ownership changes
When the new owners took over, the first big shift was the end of a cogeneration agreement to supply cold water to an adjacent Air Products facility. As the onsite 1,600-ton absorption chiller was no longer needed, it was decommissioned.
Next, FMPA took out the duct burners, which had been there since day one, as they hadn’t been used for many years. A compressor upgrade in 2008 had increased mass flow by 8% to 10%, providing the power boost previously available from duct burners.
“We didn’t need the duct burners to meet our power contracts,” said Slade. “As we hadn’t used them since 2008, FMPA took them out.”
After a review of existing assets, FMPA engaged ICT Industrial to replace the aging cooling towers, which had been constantly exposed to moisture, chemicals, UV radiation and fluctuating temperatures. Traditional materials like wood, steel, and concrete are being supplanted by advanced composites for better durability and performance.
At SLEC, the new four-cell cooling tower has a fiber-reinforced polymer (FRP) design. FRP’s polymer base is reinforced with resin-impregnated fibers that don’t oxidize like metal or decay like wood. Advantages include corrosion resistance, a high strength-to-weight ratio, low maintenance, UV and weather resistance, and a longer service life. They can be built, transported, and installed faster, and are easier to repair.

New operating mode
It is quite a change to go from 30 years of baseload to dispatch only. Slade said that in the first two months of 2026, the facility ran for six days. This is due to it being part of a much larger power pool. FMPA has many plants to call upon. Prices and demand differ across its network. Those who own the transmission lines take their own cut of the revenue, too. And the plants across its network operate at different levels of efficiency. Newer turbines with higher efficiency, for example, may be cheaper to run than an older combined cycle facility like SLEC. Those running the power pool utilize multiple factors to determine which plants operate when.
“The FMPA pool has a balancing authority and a great many assets at its disposal,” said Slade. “Some might be offline due to an outage, so they utilize all the units in the pool in the most economical way.”

Review of each asset
With more than 30 years at the helm, Slade is adjusting to the new way of doing business.
“In this new era, plants should consider immediate ways to provide more power,” he said. “You can’t acquire a new gas turbine for up to five years due to delivery backlogs, yet there is a growing need for energy. Upgrade packages have become more important as well as other ways to get more capacity out of your assets.”
The new owners of SLEC are methodically reviewing each asset with a view to the facility lasting another two decades. The plant’s original gas turbine was an ABB 11N1 configured in a single-shaft arrangement, with an ABB VAX steam turbine and a water-cooled Brush 145 MVA generator. The combined cycle configuration is single-shaft with an SSS Clutch sitting between the generator and the steam turbine.
In 2005, the gas turbine was upgraded to the Alstom GT11NM, which enhanced power output and reduced CO emissions. In 2008, Alstom released the NMC version, which consisted of a compressor upgrade and a new rotor. Now FMPA is in the process of implementing the GT11NM XL/XP upgrade from GE Vernova, which extends major inspection intervals from 24,000 to 32,000 equivalent operating hours (EOH) in the XL operation mode, improves output by 9.6 MW and efficiency by 2.9%. Alternatively, the XP operation mode keeps the maintenance interval at 24,000 EOH but boosts output by 13.1 MW and efficiency by 3.2%. This XL/XP package entails new hardware on row 4 of the compressor, cooling improvements, and upgraded controls. Hughes Technical Services is installing the package.
“We have switched from running 8,000 hours per year to where we will now have fewer hours but more starts,” said Slade. “The XL/XP upgrade will enable us to provide more MW whenever we are called upon to operate.”
FMPA is also considering electrical improvements, as up to 10 MW of output is lost due to inefficiency at the transformer, substation, and transmission lines. The proposal is to upgrade from the two aging transformers currently in place to one larger transformer and re-stream the substation connections to Duke Energy.
Duct burners are also back on the table. They may be reintroduced to gain more capacity for those times the plant is on dispatch duty, as every MW counts. Slade estimated that new burners could add 4 to 6 MW. If the price of power is high enough, the higher heat rate and extra fuel burned wouldn’t be a concern.
Spare parts, though, are increasingly problematic. Slade attends the Alstom Owners Group (AOG) every summer. This organization comprises legacy ABB/Alstom equipment owners who share information and address solutions to common issues and lack of components.
“We all help each other with obsolete parts, and there are some companies that manufacture re-engineered blades and buckets,” said Slade. “But in another ten or 15 years, it is likely to be challenging to find parts for a 50-year-old turbine.”
Sand Lake isn’t alone. Combined cycle plants built to run 8,000 hours a year are being asked to start more often, sit idle for weeks and still deliver every megawatt when called. At POWERGEN 2027, January 18-21 in Salt Lake City, owner-operators will share how they are managing cycling wear, keeping legacy turbines supplied with parts and finding more capacity in existing assets. Explore sessions on gas turbine and combined cycle, steam cycle and HRSG, and O&M and asset life on the POWERGEN agenda.
See Full Agenda | Register now
HRSG and steam turbine
As the impact of the shift in operating mode is unknown, each element of the facility is under review. FMPA has to be sure the equipment at SLEC can deal with sudden starts for short periods and then no operation for a few weeks in between.
The ABB HRSG is a dual-pressure unit with finned tube construction throughout. It has been repaired several times over the years. It is subject to regular inspections and repairs as needed. The ABB distributed control system (DCS) and gas turbine/steam turbine control system hardware from 1993 were upgraded to Alstom BlueLine technology a few years ago.
The ABB Stal steam turbine is the VAX type, structured with a dual casing with high-speed and low-speed modules connected via speed reduction gears. It is rated at 40 MW. It has a high-speed, high-pressure (10,062 RPM HP turbine) section connected via a gearbox to a 3,600 RPM low-pressure (LP) section. Boiler feed water pumps are each sized for 100% duty and are a horizontally split casing design with interstage takeoff to supply the LP steam turbine. The lifespan of the steam turbine is unknown. An upcoming scheduled outage will look into what needs to be done to keep it operating well.

Clutch
SLEC was the first single-shaft combined-cycle plant in the U.S. with a clutch rated at more than 100 MW. The SSS Clutch operates between the exciter end of the generator and the low-pressure section of the steam turbine. Many use a clutch to switch from power generation mode to the provision of ancillary services, such as spinning reserve or synchronous condensing. This is not the case at SLEC. Its purpose is to enable faster startup. Without the clutch, it would take 45 minutes or more for the plant to produce power. By disconnecting the steam turbine, the gas turbine can be started independently and can provide 10 MW within 20 minutes while the steam turbine is being prepared. The power output of the gas turbine steadily ramps up from that point while steam is brought to the right heat and pressure to run the steam turbine. The SSS Clutch can accommodate large axial movements if necessary and features high overspeed and overload capacity. It decouples steam turbine operation from that of the gas turbine. With the clutch, a steam turbine trip does not necessitate a gas turbine trip.
SSS Clutch installed a new clutch in 2017, and it is operating well. When Slade returned the original to the OEM, inspection revealed that it was running perfectly.
“We are confident we can get another 20 years of trouble-free service from our existing clutch,” said Slade.